9 3 2015 CALPEX district heating pipe CPX Subject to technical changes 3 4 1 R D 2 3 1 R D Wall seal Core bores cement liner pipes 1 420 Standard With additional centering ring Core bores Perfect bores are required for installation As hairline cracks may be present in the concrete or result from drilling it is advisable to seal the entire length of the borehole with suitable sealant such as AQUAGARD Tightness can only be guaranteed if this recommendation is fol lowed 1 CALPEX district heating pipe 2 Seal set single seal 1 x 40 mm Shore hardness D 35 3 Seal set double seal 2 x 40 mm Shore hardness D 35 4 Liner pipe made of fibre cement or coated core bore Suitable for pressure from water up to 0 5 bar Outer pipe Liner pipe core bore Seal set Core bore Ø R Ø D Ø inner Ø mm mm mm mm 76 150 78 85 150 91 150 86 94 150 111 200 105 115 200 126 200 125 135 200 142 200 137 145 200 162 250 157 165 250 182 250 180 190 250 202 300 198 207 300 225 300 225 233 300 250 350 250 259 350 Building entry see sheet CPX 1 425 Ou te r s id e of ba se m en t Ou te r s id e of ba se m en t In ne r s id e of ba se m en t In ne r s id e of ba se m en t