9 3 2015 CALPEX district heating pipe CPX Subject to technical changes 1 225 Heating strip sanitary 10 bar Planning and connection technology 1 Requirements for heating strip 1 1 Minimum power Type CALPEX UNO 32 111 40 126 50 126 40 C 5 8 W m 6 3 W m 7 3 W m 50 C 7 8 W m 8 3 W m 10 3 W m 60 C 9 6 W m 10 4 W m 12 8 W m In relation to a maintained temperature of 1 2 Recommendations for heating strip Hot water Frost protection HWAT R from Tyco Thermal Controls N V meets the FS B 2X from Tyco Thermal Controls N V requires requirement for Ø 50 126 60 C thermostat with temperature sensor UTR15 Automatic power adjustment with HWAT ECO Heating strip type HWAT R FS B 2X Fuse 13 A 16 A 20 A 10 A 16 A Length Lmax 60 m 80 m 100 m 65 m 105 m Max heating circuit length in relation to a cut in temperature of 12 C HWAT or 0 C FS B 2X Fuse protection using automatic cutouts with characteristic C 2 Joint 3 T branch For the T branch note that the sum of two connected pipes must not be Lmax T switches cannot be supplied Lmax max permitted length for heating strip L Lmax Through connection Supply Through connection L Lmax Separation of heating strip Supply SupplyEnd closure Supply End closure Through connection L Lmax Supply End closure Through connection L Lmax The heating strip and the accessories are installed by the electrician