8 1 2015 INT CASAFLEX district heating pipe CFL Subject to technical changes 4 525 Entry into building Core bore All figures in mm The connector and or the CASAFLEX pipe are not suitable for accommodating expansion of ongoing pipes A fixed point clamp must be fitted for this reason see worksheet CFL 4 515 Monitoring box on wallDetection wires Monitoring box on pipe Fixed point see text 160 CASAFLEX pipe see sheet CFL 4 115 Protective cap Connector see sheet CFL 4 330 Wire conn ection m in 2 50 Core bores Outer casing D1 A Ø D mm mm mm 91 150 180 111 200 230 126 200 230 142 200 230 162 250 280 30 A D1 All figures in mm Core bores Perfect bores are required for installation As hairline cracks may be present in the concrete or could be caused by processing it is advisable to seal the entire length of the borehole wall with suitable sealant such as AQUAGARD Tightness can only be guaranteed if this recommendation is followed Seal set type A single seal 1 x 40 mm Shore hardness D 35 Seal set type C40 double seal 2 x 40 mm Shore hardness D 35 Liner pipe made of fiber cement or core bore coated Suitable for pressure from water up to 0 5 bar