8 1 2015 INT CASAFLEX district heating pipe CFL Subject to technical changes 4 510 1 Junction with T piece 2 Transition with fixed point All figures in m 3 Transition with Z bend 4 Transition with expansion bend CASAFLEX 2 0 Joint sleeve Steel pipe FP I Connection rigid flexible CASAFLEX pre insulated steel pipe Installation instructions for transition from CASAFLEX to pre insulated steel pipe The transverse expansion l must not exceed the expansion that can be accommodated by junction pipe L1 and the CASAFLEX pipes The expansion Δl of the plastic casing pipe due to the increase in tem perature cannot be compensated by the CASAFLEX pipes Installation requires a fixed point shorter lengths are possible on request and static verification Static design of the Z bend according to expansion variable l l Expansion FP Fixed point pre insulated steel pipe EP Expansion pad Design of expansion components Positioning of expansion pads as per the section on PREMANT All figures in m L1 3 m DP Muffe KMR I KMR Muffe 2 m DP 2 m I L1 3 0 m L1 3 m Joint sleeve KMR DP Rmin I 1 0 m m